UPS Delta RT-Series 8kVA S w-20x9Ah batt. & PDB (UPS802R2RT0B035)
Product Specifications
Input parameters
- Rated power, VA/W: 8000 / 8000
- Voltage range: 100~280V (single phase, 2 wires plus ground)
- Voltage range: 100~175V with linear derating at 50~100% load
- Frequency: 40~70Hz
- Power factor: > 0.99 (at full load)
- Current harmonic distortion factor: < 3%
- Input connections: Input terminal block x 1
output parameters
- Power factor: 1
- Voltage: 200, 208, 220, 230, 240 VAC current (single phase)
- Frequency: 50/60Hz±0.05Hz
- Voltage THD: < 2% (with linear load)
- Overload capacity: ≤ 105%: continuous operation 106 ~ 125%: 5 min. 126 ~ 150%: 1 min. > 150%: 500ms
- Conclusions: IEC C13 x 6 (non-managed) IEC C19 x 4 (non-managed) Terminal block x 1 (non-managed) IEC C19 x 1 (managed)
efficiency
Normal mode: up to 95.5%
Economy mode: up to 99%
Rechargeable batteries
- Battery capacity: 20×9 Ah
- Battery voltage: 240 V DC current
- Charging current: 1.5 A (default) 8 A (maximum)
Common parameters
Noise level: 50 dB
Display Graphic LCD display with a multilingual interface
- Communication interfaces: 1 MINI slot, 1 USB port, 1 RS232 port, 1 RS485 port, 1 REPO/ROO port, 4 dry contacts
- Dimensions (W × D × H), mm: 440×750×218
- Weight, kg: 85.5
- Ambient operating temperature: 0~55°C
- Relative humidity of the environment: 5 ~ 95% (non-condensing)
Reviews